Hello!
Member Center
VIP User Benefits
选择省份
Click to view:NR Series Intelligent on&off model Actuator
Q:Can we select the minimun and maximum opening? For example, Can we use it at 10% at the minimum position and 70% at the maximum?
A:Yes, you can change it by parameter pos 0% and pos 100%.
Q:Is there the option of having two auxiliary contacts to indicate the position of the actuator?
A:No auxiliary contacts, only minimum and maximum relay, you can use 4-20ma as feedback
Q:Is there a version of these actuators that can work with a 120V supply voltage?
A:Yes, rated voltage is AC95V-265V. (Option: AC/DC24V can be customized)
Q:Is the switching speed adjustable?
A:Yes, 10 to 30 seconds ( Slower speed, lower torque.)
Q:Is the control mode adjustable ?
A:Yes, 0-20mA, 0-5V, 1-5V, 0-10V, 2-10V can be customized.